2012 New Rubber Cable
Rubber Cable
1, Standard: GB5013/IEC60245 or according to customer’s requirements
2, Voltage: 300/500V 450/750V
3, Application: Rubber cable is designed to provide high flexibility and have the capacity to withstand weather,oils/greases.Mechanical and thermal stress.Applications include handling equipment,mobile power supplies,worksites,stage and audio visual equipment,port areas &dams.Also for use in drainage and water treatment, cold environment and severe industrial environment HO7RNF cable can be permanently immersed at depths of up to 100m.They are suitable for DC solar,battery and load connections.Applications include pumps,handling equipment,mobile power supplies,worksites,stage and audio visual equipment,aquatic environment,port areas and damns.Drainage and water treatment,cold environment.
4, Nominal cross section size of conductor: 0.75 mm2, 1 mm2, 1.5mm2, 2.5mm2, 4mm2, 6mm2, 10mm2, 16mm2, 25mm2, 35mm2, 50mm2, 70mm2, 95mm2, 120mm2, 150mm2, 185mm2, 240mm2, 300mm2
5, Cores Available: Single core, 2 cores, 3 cores, 2+1 cores, 4 cores, 5 cores, 3+1 cores, 6 cores.
6, This series of rubber cables include models as below:
YC | Heavy-duty rubber cable with rubber insulation and sheath | |
YQ | Light-duty rubber cable with rubber insulation and sheath | |
YZ | medium rubber cable with rubber insulation and sheath | |
YZW | medium oil-resistant rubber cable with rubber insulation and sheath | |
YCW | Heavy-duty oil-resistant rubber cable with rubber insulation and sheath | |
7, Main technical parameter
Nominal cross section | 20 DC resistance not more than | |
tinning | Not tinning | |
0.5 | 40.1 | 39.0 |
0.75 | 26.7 | 26.0 |
1.0 | 20.0 | 19.5 |
1.5 | 13.7 | 13.3 |
2.5 | 8.21 | 7.98 |
4 | 5.09 | 4.95 |
6 | 3.39 | 3.30 |
10 | 1.95 | 1.91 |
16 | 1.24 | 1.21 |
25 | 0.795 | 0.78 |
35 | 0.565 | 0.554 |